Compliance verification activity type: Field Inspection
Team:
Regulated company: Algonquin Tinker Gen Co.
Operating company: Liberty Utilities
Province(s) / Territory(s):
Discipline(s):
Rationale and scope:
Joint integrity and environment inspection of two 69 kV transmission lines. The purpose of the inspection was to verify compliance to CSA C22.1 No.15 or earlier version of the Canadian Electrical Code, CSA C22.3 No. 15 or earlier versions for Overhead transmission lines, NERC reliability standards where applicable, and company plans, manuals, and procedures and the NEB Conditions issued by the Board in the instrument. Both lines run from the Tinker Generating Station to the USA border. Line 6901 is approximately 2.5 km long and was upgraded (restringing and pole replacement) in 2016. Line 6904 is approximately 2 km long and was built in the 1960s; it underwent a partial upgrade in 2016. The integrity scope of the inspection included maintenance of the right-of-way (RoW), the structural integrity of the line, protective relays and battery banks, and company documentation. The environmental scope of the inspection included, but was not limited to, avian protection, watercourse crossings, vegetation management, invasive species management, and environmental training and monitoring practices.
Compliance tool(s) used:
Facilities:
Facility Types
Life-cycle Phases
Regulatory requirements that apply to this activity:
Observation 1 - General Observations - Integrity
Date & time of visit: 2018-09-13 09:25
Discipline: Integrity Management
Categories:
Facility:
Observations:
General Observations:Line 6904:
Line 6901:
Compliance tool used: No compliance tool used
Observation 2 - Specific Observations on Line 6904
Date & time of visit: 2018-09-13 11:00
6904:
Observation 3 - Specific Observations on Line 6901
Date & time of visit: 2018-09-13 14:50
6901:
Observation 4 - Substation and Control Room
Date & time of visit: 2018-09-13 16:30
Substation and Control Room:Substation: The old 50 MVA 138/69 kV transformer has been replaced with the new 100 MVA 138/69 kV transformer. The associated circuit breakers are also replaced with the change. The substation grounding were checked and was found to be satisfactory.Control Room: The ATG maintains access control to both the substation and the control rooms and consistent with the requirements of the NERC CIP standards. The batteries are Gel type batteries and for 1 year old. The room also houses the A and B protective relays for both the transformer and for the 6901 and 6904 lines. The room is temperature controlled and accordingly meets the CSA 22.1 and IEEE requirements of ventilation control of the battery room.Deliverability of ATG:ATG to provide the battery test results and the routine battery test programs to the NEB by 7 December 2018.
Observation 5 - General Observations - Environment
Discipline: Environmental Protection
General
Observation 6 - Revised deliverable based on code requirements and follow-up of an outstanding deliverable
Date & time of visit: 2019-04-26 09:00
Under Item No.1 in the deliverables for Line 6904, ATG was required to submit a plan by 31 May 2019 outlining when ATG will be able to install the shield wires and implement grounding for the remaining poles of Line 6904. ATG confirmed that it was reviewing the request along with the codes and standards requirements. The NEB staff would like to clarify the following:Section 9.1.2.2.1 of CSA 22.3 No.1-15 requires that “Metal poles or the reinforcing metal of concrete poles, where such poles carry supply-line conductors” carrying supplying conductors of 22 kV or less shall be effectively grounded. No such grounding requirements are specified for towers or poles above 22 kV. However, if the towers are not effectively grounded, that may cause the following safety concerns when the tower footing resistance is too high:
Identified non-compliances to company plans or procedures are non-compliances either to:
- the condition of an authorization document that requires the implementation of that plan or procedure; or
- the relevant section of the regulations that requires implementation of that plan or procedure including those sections that require implementation of plans or procedures as a part of a Program